High vacuum transformer oil degassing plant CMM-1.0D (capacity 1000 LPH)
High vacuum transformer oil degassing plant CMM-1.0D (capacity 1000 LPH)
GENERAL INFORMATION
TECHNICAL DATA
Parameter |
Value |
|
1. Capacity, m3/h, | ||
– in degassing, dehydration and filtration mode |
0.5 – 1.5 |
|
– in heating and filtration mode |
up to 5.0 |
|
2. Capacity adjustment range, m3/h |
0.5 – 5.0 |
|
3.PedroGil Roots vacuum pump capacity, m3/h |
280 |
|
4.* Processed oil parameters : | ||
– maximum gas content, %, max. |
0.1 |
|
– maximum moisture content, ppm, |
10 |
|
– ISO 4406 industrial purity class |
9 |
|
– mechanical impurities content, ppm, max | 8 | |
– filtration rating, micron | 2…25 | |
-breakdown voltage, kV, minimum | 50 | |
5. Maximum oil outlet temperature in heating mode , ºС |
85 |
|
6. Filtration coefficient |
>50 |
|
7. Outlet pressure, MPa |
0.35 |
|
8. Delivery head, m |
35 |
|
9. Oil heater power, kW |
25.2 |
|
10. Max. oil heater mean power, W/cm2 |
1.1 |
|
11. Maximum power consumption, kW |
29 |
|
12. Power supply parameters, 3 Phases + Neutral grounded |
|
|
– voltage, V |
as required |
|
– AC frequency, Hz |
50/60 |
|
13. Dimensions w/o trailer, mm, max. |
|
|
– length |
1200 | |
– width |
1215 |
|
– height |
1610 |
|
14. Weight, kg, max. |
800 |
Note – * For inlet oil parameters as follows:
- gas content by volume less than 10,5%
- moisture content by weight less than 0,01% (100 ppm)
- temperature above 5 ºС.
TECHNICAL DESCRIPTION OF EQUIPMENT.
Configuration
The Unit (figure1.1) is an assembled container keeping all the junctions, components and aggregates. Container is the one- or biaxial trailer mounted. Front as well as back wall is lockable doors mounted for unobstructed access and fanning. Unit is supplied mounted on two-axial trailer equipped by torsional suspension axles, pneumatic wheels, coupling loop, support jacks, pneumohydraulic braking system, parking brake hand lever and electrical equipment.
There Figure 1.1. General view |
|
Figure 1.2. Unit general view
1 – vacuum column, 2 – input
pump, 3 – output pump, 4 – pipeline system, 5 – oil heater, 6 – coarse (25 micron) and fine (2 micron) filters, 7 – vacuum backing pump, 8 – booster (Roots) pump. |
Mesh filter is installed at the unit entrance and is designed for mechanical contaminants release. Filtration fineness is influenced by a 200 micron brass mesh mounted inside the case. It can be easily removed and cleaned.
Pumps 2 and 3 supply transformer oil into the Unit and suck it out respectively. The pumps are controlled from the control panel.
Coarse and fine filters 6 purify the oil being processed. Filtration fineness is 25 and 2 micron. For filter general view see figure 2.
Figure 2. Cartridge filter
1 – inlet oil pipe branch; |
The filter is lid and frame keeping one filtering cartridge inside. Filtering cartridges are made of EFMG filtering elements. To eliminate air within oil gain as well as to swallow it within oil drainage, filter uses air relieve plug. Body bottom is mounted with valve keeping branch pipe. Inlet and outlet oil branch pipes are body welded. The filtering elements (cartridges) are easy to replace and cleanable.
Figure 3. Oil heater1 – oil heating block; 2 – cold inlet oil pipe branch; 3 – heated outlet oil pipe branch |
Use separate control switch buttons for each of two heating stages to manage overall cluster. Operate either each separate or all heating sections simultaneously (mode capacity results in operating section; thus, one stage is sufficient for degassing mode as long as heating and filtering mode supposes two-stage operating). Employ temperature control sensor Th1 (Figure 6) to control oil temperature when heated. Flow
relay PП indicates operational fluid flow to prevent heating section failure and oil overheating. Heater is interlocked by a flow switch and is being energized only when oil is flowing through it. Heater is equipped with separate thermostat TS for extra-control and protection against overheating interlocked with heating elements.
Vacuum column 1 is designed for degassing of transformer oil. For column overview watch figure 4.
Figure 4. Vacuum column1 – inlet pipe branch; 2 – vacuum system connecting pipe branch; 3 – activating filter (sprayer); 4 – treated oil outlet pipe branch; 5 – level indicator; 6 – sight glass with illumination |
A shut-off valve is installed at the column for connection of vacuum system. Vacuum column includes also vacuum sensors VG1 and VG2, as well as level sensors L1 – L4.
Residual pressure of no more than 267 Pa is maintained in the column in the process of oil degassing. Oil is transported to the column by inlet pipe and through the collector to the activating filters (sprayers). Sprayer design allows for oil intensively exhaling gases and moisture.
Control cabinet is designed for placement of electrical components to facilitate Unit operation. It is a metal cabinet with lockable door. Electrical control and commutation circuits are panel located inside. Control buttons and light signaling devices are installed on the cabinet. For control cabinet general view watch figure 5.
Figure 5. General view of control cabinet panel
|
Control and measurement instruments.
Column’s residual pressure is controlled by electronic vacuum controller RVE-4.1. Limit of effective measuring range is 0,133÷105 Pa.
When operated oil heater is controlled by following measuring gauges:
- thermostat – for oil heater switch off if oil temperature is above 90 ºC set;
- flow relay – for oil heater switch off if no oil flow is supplied through oil heater;
- thermistor – for oil temperature measuring on heater outlet;
- manometers – to indicate contamination level of filter elements with regard to inlet and outlet pressure in fine filters;
- level indicators – to control oil level in vacuum column.
The unit can be operated in the following modes:
- oil pumping;
- oil heating and filtration;
- oil dehydration and degassing;
- vacuumizing of external equipment.
Testimonials about GlobeCore:
Y. A. Engineer at Electrical Company, Asia.
Professional solution to the problem of transformer oil purification, filtration and degassing is the products of GlobeCore. I recommend looking into the company’s offers.
HARRISON A. McCOY, III
CEO, U S Energy Initiatives Corporation, Inc. (OTC:USEI), Hawaiian Islands
“We have been observing operation of GlobeCore for many years: these guys really do make outstanding equipment for transformer oil regeneration in the field. Transformer’s can be services without the need to shut them down. 1 micron filtration and drying to 2 ppm are really impressive”